Switch-Pak™ with Compact Relay Controller, High or Low Detection and Control
Application
This general purpose switch package provides a complete solution for high level spill prevention with a fixed level switch point and 10A compact relay controller for pump or valve actuation. The optional flash alarm brings immediate attention to tank high level conditions. The product is typically selected for corrosive bulk storage, day tank and waste sump applications. Specify the appropriate sensor technology, material and assembly dimension.

View Larger
Features
Fail-safe relay control of pumps and valves with 0-60 second time delay
PP or PVDF construction for use in challenging corrosive environments
Offered in 3 sensing technologies for broad application coverage
Optional strobe brings immediate attention to tank alarm conditions
PP enclosure rated NEMA 4X with 300° conduit swivel base
Tech Tip Sensor Technology
The AC powered relay controller has a 10A relay, adjustable time delay, LED indicators, NO or NC invert switch and UL fire retardant PP enclosure.



            
Ultrasonic
Broadly applied in chemical, solvent, hydrocarbon and light weight oil media

Vibration
Typically applied in wastewater media with light coating and/or foaming characteristics

Buoyancy
Best applied in clean water or water-like chemical media that is non-coating or scaling.
Specifications
Length:
6" to 10' (15cm to 3m)
Switch points:
1 (set by factory)
Orientation:
± 30° vertical
Supply voltage:
120/240 VAC @ 50-60 Hz.
Contact type:
(1) SPST relay
Contact rating:
250 VAC @ 10A
Contact delay:
0-60 seconds
LED indication:
Power, relay and
sensor status
Strobe type:
_21_: Xenon tube
_22_: N/a
Strobe flash:
_21_: 1 per second
_22_: N/a
Process temp.:
F: -40° to 176°
C: -40° to 80°
Electronics temp.:
F: -40° to 140°
C: -40° to 60°
Pressure:
AU13/AZ13: 150 psi (10 bar)
AV13: 25 psi (1.7 bar)
Wetted material:
42__: PP
52__: PVDF
Process mount:
_2_3: 2" NPT
_2_7: 1 1/2" G
Enclosure rating:
NEMA 4X (IP65)
Encl. material:
_21_: PP, UL94VO & PC
_22_: PP, UL94VO
Conduit entrance:
Single, 1/2" NPT
Classification:
General purpose
CE compliance:
EN 61326 EMC
EN 61010-1 safety

Order


Home | Search | Introduction | About Flowline | What's New | Solutions Wheel | Contact Flowline
Selection Guide | Application Guide | Browse the Products | Request Catalog | New Products
My Distributor | FAQs | Tech-Tips | Case Studies | Flowline News
Glossary | Success Stories | Technical | Chemical
Request Quote | Registration | White Papers

The Flowline Liquid Intelligence and Digital Infinity logo's are all trademarks and/or service marks of Flowline. No trademark or service mark license is granted in connection with the materials contained in the Flowline web site. This web site and all of the information it contains are provided as is without warranty of any kind, whether expressed or implied. All implied warranties, including, without limitation, implied warranties of merchantability, fitness for a particular purpose, and non-infringement, are hereby expressly disclaimed. No reproduction or republication without the prior written permission of Flowline. Specifications subject to change without notice.

©1999-2009 Flowline Liquid Intelligence
10500 Humbolt Street, Los Alamitos, CA 90720 USA
Phone: (562) 598-3015 • Fax: (562) 431-8507 • Email: levelsolutions@flowline.com